Schneider Electric SpaceLogic RP-C-16A-F-230V

Schneider Electric · BACnet/IP room controller for DIN rail, powered from 230 V · RP-C-16A-F-230V

Front panel (to-scale schematic)

what it is

A programmable room controller of the EcoStruxure Building Operation system: it controls heating, ventilation and lighting of one or several rooms. The program is loaded by the integrator, and supervision is handled by an automation server, for example the AS-P.

The enclosure measures 180 × 110 × 64 mm and weighs 0.472 kg (data sheet SXWRCF16A10003). Material ABS/PC, IP20 protection, no display, one green status LED. Supply 230 V AC, up to 65 VA; a built-in transformer provides 24 V at terminals 4–5, up to 19 VA, for nearby devices. It neither accepts nor supplies PoE.

The height of 164 mm circulating in descriptions online is the dimension with the optional terminal covers. The body is 110 mm — anyone who plans a distribution board by the first number will leave 54 mm too much.

Inputs and outputs according to the data sheet:

In addition Bluetooth LE for commissioning from a mobile app (the data sheet gives a range of up to 100 m line of sight) and a clock with 7 days of backup.

what we read from it

On the network side the controller has only BACnet/IP on UDP 47808 (the port can be changed). There is no SNMP, web page or SSH — no TCP port is open. This is the correct state, not a firewall. Only silence on the BACnet port is a symptom of failure.

From the Device object we read:

For application objects — temperatures, setpoints, relays — what matters are the status flags: alarm, fault, overridden and out-of-service. The last one says that the value does not come from the sensor. Which objects exist depends solely on the integrator's program.

Reading is read-only. A write to an output object or a setpoint changes the operation of the installation, and a write with a priority can persist and override the program.

how to recognize it on the network

From the factory the controller gets its address from DHCP. When there is no DHCP server, it assigns itself an address from the 169.254 link-local pool — a controller "lost" after a replacement should be looked for there as well.

chain and ring

The two Ethernet ports are a built-in switch. Both are equivalent, so controllers are connected one after another — in a chain or in a ring protected by RSTP, which blocks one port of the loop.

The effects are visible on the network switch side:

The manufacturer's data sheet does not say whether the switch passes traffic after a loss of power to the controller. Safe assumption: a powered-off controller in a chain cuts off all those behind it.

port layout

No RJ45 port is visible from the front — only the terminal screw heads in two rows and a central strip with the LED. The drawing above is a to-scale diagram made from the manufacturer's dimensional drawing.

terminalspurpose
1–3230 V supply: L, N, protective earth
4–524 V AC output, 19 VA
6–11semiconductor outputs DO1–DO4 with commons COM1 and COM2
12–15relays DO5–DO7 with common COM3
16–18relay DO8: normally closed, common, normally open
19–30universal inputs/outputs Ub1–Ub8 with RET terminals

Between terminals 5 and 6 there is the Reset hole. The Status LED lights in the right part of the central strip.

The top edge carries two RJ45 ports RS-485 Com A and Com B. The bottom edge, from the left: USB mini-B, Ethernet 1, Ethernet 2, USB-A, the wires of terminals 19–30 and the SMA connector of the Bluetooth antenna. The manufacturer gives the order but does not dimension the ports.

pitfalls

what we cannot read

full parameter list

A full parameter list for this model is not here yet — the ones described above are those we have read and verified. A missing list does not mean the device exposes nothing more.